Time delay, sensitivity & walk test functions – CP Electronics VITP-IR User Manual

Page 7

Advertising
background image

7

4. Programming (continued)

Using the Programming Handset (Part No. DD-LCDHS)

All the following functions can be programmed using the remote control DD-LCDHS
handset:

Please note that there are some parameters that appear on the DD-LCDHS handset
which are not listed below—do not attempt to use these.

Press the ―on‖ button on the handset to switch the handset on.

Select the menu using the left and right arrows and press ―on‖.

Adjustments to each parameter can be made by using the up and down arrow
keys on the handset.

To send the selected command press the ―on‖ button whilst pointing the handset
at the detector lens. The red LED behind the detector lens will flash to show that
the command has been received.

To exit the menu, scroll right until ―Previous menu‖ appears, then press ―on‖,
which will take you back to the main menu headers, or alternatively press and
hold the left key which will also take you back to the main menu headers.

To switch the handset off, press and hold the left arrow key. On the main menu
(―Detector Param‖ will show), scroll right until ―Off‖ appears . Press the ―on‖
button‖ to turn off. The handset will switch off automatically after a time period if
left on.

1. Go to ―Detector Param‖ menu on the DD-LCDHS handset, and press ―on‖, then scroll
left and right using the left and right arrow keys through the menu to see the following
parameters.

(Factory default settings are shown in brackets):

1.1 Time mins (20 min)

(Time delay adjustment) 10 seconds to 99 minutes time

delay (select 0 for 10 second delay – use for

commissioning only).

1.2 Sens On (9)

Sensitivity level when the detector is already operational

- adjustable between 1 (min.) and 9 (max.)

1.3 Sens Off (9)

Sensitivity level for switching the detector on

– adjustable between 1 (min.) and 9 (max.).

1.4 Walk Test (N)

Select ―Y‖ for ―Yes‖ - to operate the function. An LED

behind the detector lens will flash to show movement is

being detected (use for commissioning only). Select ―N‖

for ―No‖ to cancel.

1.5 Factory Default

Restores factory default settings.

Time Delay, Sensitivity & Walk Test functions