Example of a connection

Note 1: Pt1000 temperature sensor input is calibrated in the factory with a short cable. If connection
cable of Pt1000 sensor is long, take into consideration that the impedance of connection cable has
influence on measured value. Every 3.9 Ohm of impedance of cable increases measured value by
1 Celsius degree.

Note 2: If you want to use outputs as logic (TTL output) instead of driving indication LEDs, don't use
common wires on the output connector. This wires are not connected to ground, but to power source
for LEDs. You can use common terminals of input connector or GND terminal on CUEwire connector
for connection of ground in this case. The output is able to drive the equivalent of one standard TTL
logic gate.