Installation manual

General information

With zelsius

®

C5-ISF you have acquired one of

the most up-to-date, modern heat meters cur-
rently available on the market.

Expressive symbols in the display and easy
menu navigation make readout simple. Can be
operated with one single button. It is equipped
with a long-life battery made for operation dur-
ing the initial verification validity period (5 years)
including a reserve of at least another year. The
meter can be equipped optionally with a battery
lifetime of 11 years.

MID - Initial verification

zelsius

®

C5-ISF is produced and tested in

compliance with the new European Measur-

ing Instruments Directive (MID). According to
this directive, devices are no longer carrying an
initial verification stamp, but rather the year of
the device’s declaration of conformity (recog-
nizable on the front of the device, for example:
M12). The MID controls the use of heat meters
up to the moment they are placed on the market
resp. their first putting into use. After this, the
national regulations for devices subject to com-
pulsory verification apply within the EU.
The duration of initial verification validity in Ger-
many remains 5 years for heat meters. After
this period has expired the measuring device
may no longer be used for billing in commercial
use.
The regulations resp. validity period may vary in
other countries of the EU.

2

* Standard: Ratio 25; optionally R50 but not for qp=0,6 and non-symmetrical temperature sensors installation

Technical data flow sensor ISF

Nominal flow qp

m³/h

0,6

1,5

2,5

Maximum flow qs

m³/h

1,2

3,0

5,0

Minimum flow qi horizontally*

l / h

12 / 24

30 / 60

50 / 100

Minimum flow qi vertically*

l / h

12 / 24

30 / 60

50 / 100

Starting flow horizontally ca.

l/h

4

4

5

Pressure loss at qp

bar

<= 0,25 bar

Temperature range

°C

10°C <= θ

q

<= 90°C

Minimum pressure

(to avoid cavitation)

bar

0,3

Measurement accuracy class

3

Nominal pressure

PS/PN

16

Nominal diameter

DN

15

15

20

Installation position

horizontally or vertically, no upside down installation

Installation

return flow optionally forward flow

Cable length up to calculator

(in version combi)

m

1,2

Installation place temperature sensors

M10 x 1

Heat carrier (Medium)

water