Notes ball valves

Mount ball valves up- and downstream of the
meter.

Mount a ball valve with bore M10x1 for direct
sensors in the supply. This is required for the
installation of the supply sensor

For symmetrical temperature sensor installa-
tion, mount an identical ball valve in the return.
This one is used for mounting the return sensor.

Mounting heating- / cooling energy meter

Flush the system thoroughly before installing
the heating-/cooling energy meter.

Close valves and release pressure.

Dismount the existing flow sensor or meter blank.

Use only new and flawless sealing material
and check the seal face for damage.

Install the new flow sensor according to the
correct flow direction and installation position.

Turn heat computer to desired reading position.

Information:

The best measuring results can be

achieved by mounting with horizontal diallevel.
Combi-devices are, for example, used in tight
installation points without room for the calculator
on the flow sensor or when the calculator is dif-
ficult to read. Therefore the device still remains

easy to read enabling optimum use of the space
available for installation of the flow meter.

Installing the temperature sensor

The installation of the temperature sensors
should be preferably symmetrical and direct
installation.

Do not remove the return sensor if already
mounted in the VMU.This is also valid for all
the safety seals which are mounted on the de-
vice as standard.

Sensors are colour-coded (red = supply, blue
= return).

The connecting cables may not be buckled, ex-
tended or shortened.

The seal at the sensor installation point on the
measuring capsule may not be damaged.

Remove locking screw and seal at the ball
valve completely, if existing.

Attach the O-ring to the installation aid (the 2nd
O-ring is only a spare O-ring).

Using the installation aid, insert the O-ring into
the installation point according to DIN EN 1434
with a slight circular motion.

Using the other end of the installation aid bring
the O-ring into the correct position.

Insert the 2 halves of the plastic connector into
the sensor’s three notches (crimps) and press
them together.

Use the installation aid as positioning aid.

Insert the temperature sensor into the installa-
tion point and screw it in tightly until the dead
stop of the seal on the 12-point is reached
(mounting torque 3-5 Nm).

The sensor optional integrated in the VMT has
to be secured

Secure the sensor after installation against
unauthorised removal with appropriate sealing
(available as a sealing set).