Insert Placement Requirements

 The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,

doors), 36" (915mm) of the front of the insert (item “q” below).

 Insert and hearth must be installed on a level, secure floor
 The minimum clearances, facing, and hearth requirements listed below must be met.

Minimum Clearances

k Sidewall

11.625" 296mm

l Side Facing (non-combustible)

6.25" 159mm

m Top Facing (non-combustible)

37.5" 953mm

n Mantel (combustible – maximum 12” 305mm deep)

37.5" 953mm

o Front Hearth

16” 407mm

(USA)

18” 458mm

(Canada)

p Side Hearth

8" 204mm

q Front of Insert

36" 915mm

s Mantel Column (max. 8” 204mm deep)

6.25" 159mm

x Extension Onto Hearth

1.5" 39mm

Combustible Top Facing

Side

Wall

Non-Combustible

Hearth

Facing

q

l

p

o

m

Combustible Mantel

n

k

s

x