curve E (extremely inverse) selected (SW3-3 set to OFF) and the TIME DIAL set to 2.0. The feeder
reclosing relay is set for two reclose attempts at 3 and 15 seconds after the initial trip. If a permanent fault
occurs (magnitude ten times pickup), calculate the feeder breaker trip time for each of the three
operations. Refer to Section 1 for characteristic curve constants.

From the time characteristic curve equation.

K

BD

C

M

AD

T

N

Trip

028

0

2

02758

.

0

1

10

2

7624

7

0938

2

.

.

.

028

0

05516

.

0

1

10806

124

5248

15

.

.

.

seconds

0.209

From the reset characteristic curve equation.

1

M

RD

T

2

Reset

seconds

15.5

1

0

2

7.75

2

M = 0 if current goes to zero.

Negative result indicates reset time.

Results:

Full trip = 0.209 seconds and full reset = 15.5 seconds if current goes to zero.

In Figure 4-1,

T

A

= 0.209 seconds (relay was at reset).

T

B

= value < T

A

because rewind has not gone to zero.

T

C

= value < T

A

because rewind has not gone to zero.

9252000896 Rev B

BE1-50/51B-232 Installation

4-5