Equation for time to trip during rewind (before relay is reset).



Rewind

Full

Time

Rewind

Trip

Full

T

Occurence

This

Trip

Second Operation

 

15.5

3

0.209

T

B

seconds

0.040

T

B

Third Operation



15.5

11.96

0.209

T

C

seconds

0.161

T

C

CONNECTIONS

NOTE

Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG
copper wire attached to the ground terminal on the rear of the unit case. When
the relay is configured in a system with other devices, it is recommended to use a
separate lead to the ground bus from each unit.

Typical ac input and dc control connections are shown in Figures 4-6 and 4-7. Refer to the block diagram
in Section 3 for relay internal connections.

Figure 4-6. AC Input Connections

4-6

BE1-50/51B-232 Installation