Basler Electric BE1-59N User Manual

Page 18

Advertising
background image

Locator

Description

D

Undervoltage Time Dial. Pushbutton switch that selects the desired overvoltage output

delay, either definite time (from 00.1 to 99.9 seconds) or, inverse time (characteristic

curves 01 through 99). A setting of 00 is instantaneous in either case.

E

Power Indicator. This red LED lights when operating power is applied to the relay.

F

Target Reset Switch. This switch is operated to reset the target indicators.

G

Target Indicators. The electronically latched red target indicators illuminate when the

corresponding output relay energizes. To ensure proper operation of current-operated

targets, the current flowing through the trip circuit must be 200 mA or higher. Target

indicators are reset by operating the target reset switch (locator F).

H

Output Test Pushbuttons. These pushbuttons allow manual actuation of the output relays.

Output relay actuation is achieved by inserting a nonconductive rod through the front

panel access holes.

I

Undervoltage Pickup LED. A red LED that illuminates when undervoltage exceeds the

pickup setting.

J

Undervoltage Pickup Adjustment. A multiturn potentiometer that sets the undervoltage

comparator threshold voltage. Continuously adjustable over the range indicated by the

style chart.

K

Inhibit LED. A red LED that illuminates when the monitored generator voltage is under the

inhibit set point.

L

Inhibit Pickup Adjustment. Multiturn potentiometer that sets the inhibit comparator

threshold so that whenever generator voltage falls below the set point, the (optional)

undervoltage measuring circuitry is inhibited from operation.

2-2

BE1-59N Controls and Indicators

9171400990 Rev K