General information, Purpose, Application – Basler Electric BE1-59N User Manual

Page 9: High resistance grounding, Section 1 • general information -1, Purpose -1, Application -1, High resistance grounding -1

Advertising
background image

SECTION 1 • GENERAL INFORMATION

PURPOSE

The available fault current for single-phase-to-ground faults is very limited for ungrounded systems and

systems, which are grounded through a high resistance. This current limiting reduces the possibility of

extensive equipment damage, and eliminates the need for a neutral breaker by reducing the fault current

below the level required to sustain an arc. However, it remains important to detect and isolate single-

phase-to-ground faults in order to prevent their evolution into more dangerous faults such as phase-to-

phase-to-ground and three-phase-to-ground faults. Sensitive voltage relays can be used to detect ground

faults where the fault current is very small. The BE1-59N Ground Fault Overvoltage Relay is especially

suited to this task.

APPLICATION

High Resistance Grounding
A common method of grounding an ac generator is to connect a distribution transformer between the

neutral of the generator and the station ground. The distribution transformer's primary voltage rating is

equal to, or greater than, the generators rated line-to-neutral voltage. The distribution transformer

secondary is rated at 200/240 Vac or 100/120 Vac, and a resistor is connected across the secondary

winding. When reflected through the transformer, the resistor is effectively a high resistance.

R

p

= R

s

x N

2

Where:

R

p

is the effective primary resistance

R

s

is the actual value of the secondary resistor

N is the turns ratio of the distribution transformer

To determine resistor sizing:

Determine the thermal limit P (in watts) of the voltage transformers.

Use

R

Vpri

V

=

2

sec)

(

to determine resistance in ohms, where Vsec = 120 x 3 = 360V. This assumes a

120V VT secondary in a worst-case condition.

Size the watt rating of the resistor for 1/3 of the VT thermal limit to keep the resistor from excessive

heating. A smaller watt rating can be used if tripping for a ground condition.

Available single-phase-to-ground fault current at the generator terminals is greatly reduced by the high

effective resistance of the distribution transformer and secondary resistor. The distribution transformer

provides isolation for the protection scheme and reduces the voltage to a convenient level.
The BE1-59N Ground Fault Overvoltage Relay is connected across the secondary resistor to detect the

increase in voltage across the distribution transformer caused by a ground fault in the generator stator

windings. A ground fault at the generator terminals will result in rated line-to-neutral voltage across the

transformer primary, while ground faults near the neutral will result in lower voltages. The overvoltage

relay setpoint must be higher than any neutral voltage caused by normal unbalances in order to avoid

nuisance trips. This will allow a certain percentage of the stator windings to go unprotected by the

overvoltage relay. The overvoltage relay function typically protects 90 to 95% of the generator stator

windings.
The BE1-59N Ground Fault Overvoltage Relay monitors the fundamental frequency (50 or 60 Hz) voltage,

which accompanies a ground fault, but is insensitive to the third harmonic voltage present during normal

operation. One hundred percent protection of the generator stator windings is obtainable with the optional

overlapping undervoltage element. The under voltage element is tuned to the third harmonic voltage

which is present in the generator neutral under normal conditions. The undervoltage element detects the

reduction of the normal third harmonic voltage, which accompanies a ground fault near the neutral point

of the generator.
An undervoltage inhibit feature is included with the third harmonic undervoltage element. This feature

supervises the operation of the ground fault relay to prevent operation during startup and shutdown by

monitoring the generator terminal voltage.

9171400990 Rev K

BE1-59N General Information

1-1

Advertising