Continuation Software Description

Binary Output Object 1…2

Property

Remark / Value

RW

Object_Identifier

binary-output, instance 1 … 2

R

Object_Type

BINARY_OUTPUT (4)

R

Object_Name

max. 42 Bytes, default “Relay 1” … “Relay 2”

RW-E

Description

max. 84 Bytes, default “”

RW-E

Present_Value

NULL (write only) / INACTIVE (0) / ACTIVE (1)

RW

Status_Flags

IN_ALARM: 0
FAULT: 0
OVERRIDDEN:

0 = Switch A (Auto)

1 = Switch 0 (Off) or 1 (On)

OUT_OF_SERVICE: 0 / 1

R

Event_State

NORMAL (0)

R

Out_Of_Service

FALSE (0) / TRUE (1)

RW

Polarity

NORMAL (0) / REVERSE (1)

RW-E

Priority_Array [16]

NULL / INACTIVE (0) / ACTIVE (1)

R

Relinquish_Default

INACTIVE (0)

R

Inactive_Text

max. 20 Bytes, default “Off”

RW-E

Active_Text

max. 20 Bytes, default “On”

RW-E

Notification_Class

Unsubscribed UnconfirmedCOVNotification
0: no COV notification, default,
1: local broadcast,
2: global broadcast

RW-E

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash

Function Table for Binary Output

Out_Of_Service

Polarity

Switch

Priority_Array

Present_Value

Binary Output

OVERRIDDEN

OUT_OF_SERVICE

0

0

A

NULL / 0 / 1

0 / 0 / 1

0 / 0 / 1

0

0

0

0

0
1

NULL / 0 / 1
NULL / 0 / 1

0
1

0
1

1

0

0

1

A

NULL / 0 / 1

0 / 0 / 1

1 / 1 / 0

0

0

0

1

0
1

NULL / 0 / 1
NULL / 0 / 1

1
0

0
1

1

0

1

0

A

NULL / 0 / 1

0 / 0 / 1

0

0

1

1

0

0
1

NULL / 0 / 1
NULL / 0 / 1

0 / 0 / 1
0 / 0 / 1

0
1

0

1

1

1

A

NULL / 0 / 1

0 / 0 / 1

1

0

1

1

1

0
1

NULL / 0 / 1
NULL / 0 / 1

0 / 0 / 1
0 / 0 / 1

0
1

0

1

Continuation Software Description

Binary Input Object 1…4

Property

Remark / Value

RW

Object_Identifier

binary-input, instance 1 … 4

R

Object_Type

BINARY_INPUT (3)

R

Object_Name

max. 42 Bytes, default “Input 1” … “Input 4”

RW-E

Description

max. 84 Bytes, default “”

RW-E

Present_Value

INACTIVE (0) / ACTIVE (1),
writable if Out_Of_Service

R
RW

Status_Flags

IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE:

0 / 1

R

Event_State

NORMAL (0)

R

Out_Of_Service

FALSE (0) / TRUE (1)

RW

Polarity

NORMAL (0) / REVERSE (1)

RW-E

Inactive_Text

max. 20 Bytes, default “Off”

RW-E

Active_Text

max. 20 Bytes, default “On”

RW-E

Notification_Class

Unsubscribed UnconfirmedCOVNotification
0: no COV notification, default,
1: local broadcast,
2: global broadcast

RW-E

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash

Function Table for Binary Input

Out_Of_Service

Polarity

BinaryInput

Present_Value

OUT_OF_SERVICE

0

0

0
1

0
1

0

0

1

0
1

1
0

0

1

0

0
1

x

1

1

1

0
1

x

1

x: Present_Value is writable and not affected by inputs

Group Object 1…3

Property

Remark / Value

RW

Object_Identifier

group, instance 1 … 3

R

Object_Type

GROUP (11)

R

Object_Name

max. 42 Bytes, default “Group 1” … “Group 3”

RW-E

Description

max. 84 Bytes, default “”

RW-E

Present_Value

Present_Value of Binary Inputs,
see next Table

R

List_Of_Group_Members

see next Table

R

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash

Members of Groups

Group

Binary Input
1

2

3

4

1

x

x

x

x

2

x

x

3

x

x