Contemporary Control Systems Modbus Cube I/O MR-SI4 User Manual

Digital input module mr-si4

Advertising
background image

METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433
Mounting instruction see www.metz-connect.com

1. Description

The Modbus module with 4 S0 inputs to DIN EN 62053-31 class A
was developed for decentralized switching tasks. It is suitable for
counting S0 counter pulses. This allows very good integration of the
module into an energy controlling system. In case of a power failure,
the last counter readings are saved. The inputs can be scanned
by means of standard objects via a Modbus master. The module
address, the baud rate and the parity are set by means of two
address switches on the front.
Suitable for decentralized mounting in serial sub-distributor.

2. Declaration of Conformity

The device was tested according to the applicable standards. Con-
formity was proofed. The declaration of conformity is available at
the manufacturer METZ CONNECT GmbH.

Notes Regarding Device Description

These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these
instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other countries
it applies to the equipment installer or the user to meet the
national directions.

Safety Instructions

Keep the applicable directions for industrial safety and prevention of
accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation or
maintenance of the devices.
Only qualified personnel shall do mounting and installation work
with the devices, see section “qualified personnel”.
The information of these instructions have to be read and under-
stood by every person using this device.

Symbols

Warning of dangerous electrical voltage

Danger

means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.

Qualified Personnel

Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices and
whose professional qualification meets the requirements of their
work.
This includes for example:

• Qualification to connect the device according to the VDE

specifications and the local regulations and a qualification to put
this device into operation, to power it down or to activate it by
respecting the internal directions.

• Knowledge of safety rules.

• Knowledge about application and use of the device within the

equipment system etc.

3. Technical Data

Modbus Interface

Protocoll

Modbus RTU

Transmission rate

1200 ... 115200 Bd

(factory setting 19200 Bd Even)

Cabling

RS485 two wire bus with voltage

equalizing cable in bus / line topology

terminate with 120 Ohms

Supply

Operating voltage range

20 ... 28 V AC/DC (SELV)

Current consumption

170 mA (AC) / 65 mA (DC)

Relative duty cycle

100 %

Input

4x S0 input according to DIN EN 62053-31 Class A

Housing

Dimensions WxHxD

1.4 x 2.8 x 3.0 in. (35 x 70 x 65 mm)

Weight

95 g

Mounting position

any

Mounting

standard rail TH35 per IEC 60715

Mounting in series

the maximum quantity of modules

without space

connected in line is limited to 15 or

to a maximum power consumption of

2 Amps (AC or DC) per connection to

the power supply. For any similar

block of additional modules a

separate connection to the power

supply is mandatory.

Material
Housing

Polyamide 6.6 V0

Terminal blocks

Polyamide 6.6 V0

Cover plate

Polycarbonate

Type of protection
(IEC 60529)
Housing

IP40

Terminal blocks

IP20

Terminal blocks

Supply and bus
4 pole terminal block

max. AWG 16 (1.5 mm²) solid wire

max. AWG 18 (1.0 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max. 1.4 mm

(terminal block and jumper plug are

included to each packing unit)

Module connection
Input/Output

max. AWG 12 (4.0 mm²) solid wire

max. AWG 14 (2.5 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max 2.7 mm

Temperature range

Operation

-5 °C ... +55 °C

Storage

-20 °C ... +70 °C

Protective circuitry

polarity reversal protection of

operating voltage

polarity reversal protection of supply

and bus

Display

Operating and bus activity green LED
Error indication

red LED

Status of the inputs

yellow LED

5. Connection Diagram

24 V AC/DC

GND

BUS B+

BUS A-

GND

B+

A-

+24V

B+

A-

S04-

+24V

GND

S04+

S03- S03+

S01+ S01-

S02+ S02-

4. Wiring Diagram

A1/ +24V

A2/ GND

BUS B+

BUS A-

24V

RISC - CPU

24V AC / 170mA

24V DC / 65mA

GND, Class 2

S01+
S01

S04+
S04

S02+
S02

S03+
S03

Modbus RTU on RS-485

Digital Input Module

MR-SI4

11083913

8096/899360