Flowserve Valtek StarPac 1 Intelligent Control Systems User Manual

Page 27

Advertising
background image

41-27

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

Failure

Probable Cause

Corrective Action

Local display not on

1. 24 VDC not on or set correctly

1. Verify power supply is outputting 24 VDC

(+3 volts) at terminals 1 and 2

2. Incorrect wiring polarity

2. Check wiring for correct polarity

3. Interface connections on bottom

3. Make sure connections are correctly

are not correct

aligned and fully plugged in

Local display has black

1. RESET switch was left down or

1. Set RESET switch to up position or boxes

showing dimly

system not completely initialized

completely reinitialize system

Erratic communications

1. Multiple units have same address

1. Change each unit to a unique, sequential

on network line

address (refer to Address Setting in
Maintenance section)

2. Proper polarity not maintained

2. Check all network connections for cor-

rect positive and negative connections

3. Individual units not properly wired

3. Begin with shortest RS-485 run, check-

ing polarity and communication; continue
checking units throughout network

4. Termination jumper not installed

4. Install termination jumper on two most

distant devices

StarPac does not

1. StarPac still in initialize mode

1. Be certain the INIT switch is up, then

respond to analog

change the mode in the tuning screen

commands

2. I/P not connected

2. Be certain the two-wire cable is con-

nected on the bottom board

StarPac data is not

1. Improper configuration file was

1. Find the correct file for this system and

correct

loaded onto system

send to the StarPac; refer to the Utility
or Technician sections of the StarPac
manual

Valve position reading

1. Hallpot connection not tight

1. Tighten hallpot connection set screw

is not correct

2. Stroke not calibrated

2. Calibrate valve stroke; refer to

Calibration section

3. Hallpot shaft is at end of stroke

3. Readjust hallpot shaft connection; make

sure shaft does not reach rotation stop
in either direction

Stem position

1. Hallpot wiring harness is installed

1. Reverse three-wire harness

decreases when valve

backwards

opens

Troubleshooting StarPac Intelligent Control Systems