Wiring, Commissioning – Flowserve TRG5-53 User Manual

Page 11

Advertising
background image

11

Wiring

Wiring diagram

See wiring diagram on page 3.

Tools

Screwdriver for slotted screws, size 2.5, completely insulated to VDE 0680

TRG 5-5...

Use four-core cable for wiring:

1. Connect terminal strip acc. to wiring diagram. Fig. 1, Fig. 2

2. You can connect additional equipment to the terminals marked in yellow and black

of the TRG 5-54, TRG 5-56 and TRG 5-58. Fig. 2

Commissioning

Use the following table indicating the resistance of the Pt 100 to ascertain the current
temperature of the fluid.

1. Connect the test wire direct to the terminal box.

2. Measure the resistance with an ohmmeter.

3. Find the corresponding value in the table below, read off the temperature and, if

necessary, determine the exact value by interpolation.

Measure fluid temperature

°C

0

10

20

30

40

50

60

70

80

90

100

/deg

10

0

100.00 103.90 107.79 111.67 115.54 119.40 123.24 127.07 130.89 134.70 138.50 0.385

100

138.50 142.28 146.06 149.82 153.57 157.32 161.04 164.76 168.47 172.16 175.84 0.373

200

175.84 179.51 183.17 186.82 190.46 194.08 197.70 201.30 204.88 208.46 212.03 0.361

300

212.03 215.58 219.13 222.66 226.18 229.69 233.19 236.67 240.15 243.61 247.06 0.350

400

247.06 250.50 253.93 257.34 260.75 264.14 267.52 270.89 274.25 277.60 280.93 0.338

500

280.93 284.26 287.57 290.87 294.16 297.43 300.70 303.95 307.20 310.43 313.65 0.327

600

313.65 316.86 320.05 323.24 326.41 329.57 332.72 335.86 338.99 342.10 345.21 0.315

700

345.21 348.30 351.38 354.45 357.51 360.55 363.59 366.61 369.62 372.62 375.61 0.304

800

375.61 378.59 381.55 384.50 387.45 390.38

0.295

Basic resistance values according to DIN 43760 for Pt 100