Flowserve TRG5-53 User Manual

Page 8

Advertising
background image

8

Function

The temperature sensors TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-56, TRG 5-57,
TRG 5-58 feature standardized platinum resistance thermometers Pt 100 according
to DIN IEC 751. The temperature sensor in combination with temperature switches
TRS 5-6 or TRS 5-8 are used for temperature monitoring. The power source is
equipped with an adjustable resistor and supplies the resistance thermometer
Pt 100 with a constant current. The desired switch-off temperatures are adjusted with
the aid of the 8 pole code switch on the temperature switch. To ensure a fail-safe
alarm in the event of excessively high temperatures the circuit features relays of the
normally-closed type. In the event of a power failure the temperature switch will raise
an alarm.

System description

The equipment TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-56, TRG 5-57, TRG 5-58 are
temperature sensors according to DIN 3440.

The temperature sensing element Pt 100 integrated in the protection tube has
temperature-dependent resistance values. The temperature switch TRS 5-6 / TRS 5-8
measures the resistance values and raises a temperature alarm correponding to the
adjusted limit.

Application in steam boilers and pressurized hot-water plants acc. to TRD 604 and
other heat-generating units.

Design

TRG 5-53, TRG 5-54:

Temperature sensor with protection tube and ½" screwed terminal box to DIN IEC 751.
The temperature sensing element can be removed.

TRG 5-55, TRG 5-56, TRG 5-57, TRG 5-58:

Temperature sensor with protection tube and socket-weld end to DIN IEC 751.
The temperature sensing element can be removed.

Explanatory Notes

Scope of supply

TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-56, TRG 5-57, TRG 5-58

1 Temperature sensor
1 Installation manual

F

F

Advertising
This manual is related to the following products: