10.5 Show gain setting

If the actuator position is unstable or self-oscillating after calibration, the gain can be adjusted.
Gain can be set from A (lowest) to G (highest). Default is D.


To show the current gain setting, press the calibration button 4 times.
X4

To indicate the current setting, the

LED’s flashes according to the following:

Y R R
LED’s show: gain is set to “G” (Highest)

Y R Y

LED’s show gain is set to “F”

Y R G

LED’s show gain is set to “E”

Y G

LED’s show gain is set to “D” (Default)

Y G G

LED’s show gain is set to “C”

Y G Y

LED’s show gain is set to “B”
Y G R
LED’s show gain is set to “A” (Lowest)

The gain code sequence is repeated 5 times



Button functions:

Press 5 sec = Calibration

Press x3 = Direct/reverse action

Press x4 = Show gain setting

Press x5 - x11 = Change gain

setting


To indicate that a command is accepted, the three LED:s

light up.