Trouble shooting – Flowserve APEX A9000 Accord User Manual

Page 33

Advertising
background image

33





The output signal on pin 9 and 10 will continue to follow the input signal instead of the position. Apply 20.0 mA input
signal. Measure the output signal and adjust the input signal up/down until the output signal is 20.0 mA. Push the
button three times until all LEDs are lighted.

The LEDs will start flash yellow-yellow and the unit is ready for continued calibration.

Press the button for 5 sec until the LEDs start alternating, Apex A9000 starts to calibrate stroke.

After calibration the unit will start running in normal operation.

13. Trouble shooting

13.1 Apex A9000 Normal operation

G

Normal operation.

Y

Valve fully closed or open

”Cut off” enabled.

13.2

Calibration

R G

(No movement)

No air supply or

shaft do not move.

Check air supply

Check shaft movement.

R Y G

Pot not calibrated.

Calibrate the pot.

R G R

Hallsensor value too low.

R R G

Hallsensor span too low.

Check hallsensor
connection.

R Y R

Hallsensor value too high.

Y R

Unit in Factory Mode.

Calibrate 4 - 20 mA

input signal.

Y G

4 - 20 mA feedback installed.

Calibrate output.