Specifications – Flowserve APEX A9000 Accord User Manual

Page 4

Advertising
background image

4




5. Specifications

5.1 Technical data

Input signal

4-20 mA Current supply min.

3,6 mA

Current supply Max.

150 mA

Load Standard

400 ohm at 20mA Load HART

470 ohm at 20mA

Voltage dropStandard

8 VDC at 20mA Voltage drop HART

9.4 VDC at

20mA Angle of rotation min

0-40°

Angle of rotation Max

0-90°

Air supply range

1.5

– 6 bar

Out put

0-100% of air supply pressure

Air supply quality

Free from oil, dust and moisture IEC 770,

ISA 7.0.01

Air supply effect

<0.1%FS for10% pressure change at 6 Bar

Ingress protection

IP66 / Nema 4X

Operating humidity

0-100% rh non-condensing

Air connections

1/4” NPT

Cable entry

2 x 1/2” NPT or 2 x M20x 1,5

Terminals

Screw terminals 2,5 mm

2

(AWG 14)

Operating Temperature

-20 to +85°C-40 to +85°C (optional)

Storage temperature

-40 to +85°C

Air delivery capacity

7 Nm

3

/h @ 6 bar (3 bar diff pressure)

Air delivery capacity Double acting

7 Nm

3

/h @ 6 bar (3 bar diff pressure)

Air consumption Single acting

0,120 Nm

3

/h @ 6 bar

Air consumption Double acting

0,120 Nm

3

/h @ 6 bar

Cv air delivery Single acting

0,12

Cv air delivery Double acting

0,12

Cut off function

Close 0.5% Open 99.5%

Linearity

<1%

Sensitivity

<0.05%

Resolution

<0,1%

Repeatability

<0.2%

Hysteresis + dead band

<0.5%

Temp effect

<0.1%/10K

Mounting position effect

<0,2%

CE

93/68/EEC, 2004/108/EEC, 2006/95/EEC

Approvals

Ex II G Ex ia IIC T4 Ta: 85°C

Class I Division 2 Groups A,B,C,D T4 non-incendive with fieldwiring

Class I Division 2 IIC T4 non-incendive with fieldwiring

I.S. Class I Division 1 Groups A,B,C,D T4

I.S. Aex ia IIC T4

Certificate nr

Nemko 08ATEX1362X

Housing material

Die cast Aluminium

Surface treatment

Powder coating

Soft goods

Nitrile

Weight

1,5 kg (3.0 kg Explosion proof version)












Advertising