4 transducer block object – Flowserve Limitorque MX DeviceNet Field Unit User Manual

Page 26

Advertising
background image

Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05

26

Table 4.31 – Continued

Attribute ID Access Rule Name

Data

Type

Description of

Attribute

Semantics of Value

21

Get/Set

(V-RW)

DO_ESD_

Poll_Cnxn

BOOL

Command emer-

gency shutdown

from

Poll Connection

Section 4.2.9

22

Get/Set

(V-RW)

DO_ESD_

Bit_Strobe_Cnxn

BOOL

Command emer-

gency shutdown

from

Bit-Strobe

Connection

Section 4.2.9

23

Get/Set

(NV-RW)

Enable_

Broadcast_

ESD_Ctrl

BOOL

Enable device to

be a part of the

broadcast

ESD control scheme

from Bit-Strobe

Connection

Section 4.2.9

0 = Disable (Default)

1 = Enable

4.4 Transducer Block Object

Table 4.32

Attribute ID Access Rule Name

Data Type

Description

Semantics of Value

1

RW

Setp_Cutoff_Dec

UINT

When the servo

setpoint goes below

the defined percent

of span, the position

goes to the limit

position CLOSE

Range 0 – 1000

Default = 0

2

RW

Setp_Cutoff_Inc

UINT

When the servo

setpoint goes above

the defined percent

of span, the position

goes to the limit

position OPEN

Range 0 – 1000

Default = 0

3

RO

Scaled_values_0

WORD

APT/ATT scaling

information

See Table 4.33

4

RO

Scaled_values_1

WORD

APT (Modbus

Register 3)

Engineering Use

5

RO

Scaled_values_2

WORD

ATT (Modbus

Register 4)

Engineering Use

6

RO

TP_Status_0

UINT

Reserved

Engineering Use

7

RO

TP_Status_1

UINT

Start_Position

Engineering Use

8

RO

TP_Status_2

UINT

Stop_Position

Engineering Use

9

RO

TP_Status_3

UINT

Num_Samples

Engineering Use

10

RO

TP_Status_4

UINT

Max_Torque_Mid

Engineering Use

11

RO

TP_Status_5

UINT

Max_Torque

Postion

Engineering Use

12

RO

TP_Status_6

UINT

Avg_Torque

Engineering Use

13

RO

TP_Status_7

UINT

Stop_Torque

Engineering Use

14

RO

TP_Status_8

UINT

Max_Torque_BOT

Engineering Use

15

RO

TP_Status_9

UINT

Maz_Torque_EOR

Engineering Use

16

RO

TQ_Status_0

UINT

Reserved

Engineering Use

17

RO

TQ_Status_1

UINT

MB_TQ_Close_

Avg_Last

Engineering Use

18

RO

TQ_Status_2

UINT

MB_TQ_Open_Avg_

Last

Engineering Use

19

RO

TQ_Status_3

UINT

MB_TQ_Open_

Peak_Last

Engineering Use

Continued on next page

Advertising