1 identity object instance attributes – Flowserve Limitorque MX DeviceNet Field Unit User Manual

Page 29

Advertising
background image

29

Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05

flowserve.com

Table 4.34

Bit 15 - 11

Bit 10 - 9

Bit 3

Unused

Scaling 0 =

0 – 100 1 =

0 – 255 2 =

0 -4095 3 =

Reserved

Unused

4.4.1 Identity Object Instance Attributes

Table 4.35 – Identity Object Instance Attributes

Attribute

ID

Access Rule Name

Data Type Description of

Attribute

Semantics of Value

1

Get

(NV-RO)

Vendor ID

UINT

Identification of

each vendor by

number

966 (3C6hex)

(Note 1)

2

Get

(NV-RO)

Device Type

UINT

Indication of general

type of product

00hex

(Generic Device)

3

Get

(NV-RO)

Product Code

UINT

Identification of a

particular product

of an individual

vendor

19800 (4D58hex)

(Note 2)

4

Get

(NV-RO)

Revision

STRUCT

of

Revison of the item

the Identity Object

represents

1.1

(Note 3)

Major Revision

USINT

Major Revision of

DeviceNet

Limitorque Interface

Minor Revision

USINT

Minor Revision of

DeviceNet

Limitorque Interface

5

Get

(V-RO)

Status

WORD

Summary status of

device

(Note 4)

6

Get

(NV-RW)

Serial Number

UDINT

Serial number of

device

(Note 5)

7

Get

(NV-RW)

Product Name

SHORT_

STRING

Human readable

identification

”Flowserve MX”

(Note 6)

8

Get

(V-RO)

State

USINT

Present state

of the device as

represented by

the state transition

diagram

10

Get/Set

(NV-RW)

Heartbeat Interval

USINT

The nominal interval

between heartbeat

messages in

seconds

The default value

is 0. Zero disables

transmission of the

heartbeat message.

100

Get

(V-RO)

EEPROM Failure

BOOL

Result of EEPROM

checksum

verification

0 = EEPROM contents

is o.k.
1 = EEPROM contents

may be defective due

to checksum error

The further optional attributes

Configuration Consistency Value (Attribute ID 9)

Active Language (Attribute ID 11)

Supported Language List (Attribute ID 12)