Product Specification

Rel.
Index

Parameter

Factory
Default

Description

25

OPERATION

Note 1

Configures the piezo/coil elements for single or dual coil operation.
Single Readback (single coil devices only) permits digital feedback
of switch status to DO-1 Function Block.

26 OUTPUT_CONFIGUR

ATION

Note 1

Configures the piezo/coil signals to shut-off or remain energized
after TIME_OUT period. Applies to Dual Coil mode only.

27

ODOMETER

This variable counts the transitions from open to closed and
closed to open states. It is reset-able to 0, after maintenance.

28

RESET_ODOMETER

Resets the ODOMETER counter.

29 FAILURE_RECOVERY

Enable/Disable

FAILURE_RECOVERY action.1: Act with or

without change in the input, 2: Do not act until a new change in the
input.

30

RESET_TIMEOUT

Resets a TIME_OUT occurrence.

31

TRANSITION_TIME

How much time for the last transition.

32

TIME_OUT

10

The time allowed for a transition before the DI associated with the
TIME-OUT Alarm is Activated. Also, the length of the One-Shot
pulse voltage output to the coils in the Dual Coil Operation Mode.

33

CLOSED_SWITCH

SW1 state

34 OPEN_SWITCH

SW2

state

35

TRANSITION_ALARM

DI-1 state = transition TIME-OUT state;

36

EXTERNAL_ALARM

DI-2 state = It read the status of the external input. Data is passed
on to DI-2.

37

ACTION_TIME

Time since last command for transition.

Notes:
1. Selected by Factory in accordance with customer PO specifications.

Transducer Block Parameter Specifications

Rel.

Index

Parameter Mnemonic

Data

Type

Size

Valid

Range

Units

Class

1 ST_REV

Unsigned

16

2

Positive

N/A

Read

2

TAG_DESC

Visible String

32

String Data

N/A

R/W

3 STRATEGY

Unsigned

16

2

N/A

R/W

4 ALERT_KEY

Unsigned

8

1

1-255

N/A

R/W

5 MODE_BLK

DS-69

4

N/A

R/W

6 BLOCK_ERR

Bit

String

2

N/A

Read

7 UPDATE_EVT

DS-73

5

N/A

Read

8 BLOCK_ALARM

DS-72

13

N/A

Read

9 TRANSDUCER_DIRECTORY Unsigned

16

Array

Variable

N/A

Read

10

TRANSDUCER_TYPE

Unsigned 16

2

E

Read

11 XD_ERROR

Unsigned

8

1

N/A

Read

12 COLLECTION_DIRECTORY

Unsigned

32

Array

Variable

N/A

Read

13

FINAL_VALUE_D

DS-66

2

N/A

R/W

14 ACT_FAIL_ACTION

Unsigned

8

1

0=Undefined

1=Close

2=Open

3=Last

E R/W

15 ACT_MAN_ID

Unsigned

32

4

E

Read

16

ACT_MODEL_NUM

Visible String

32

String Data

N/A

Read