32

9.6 DeviceNet

DeviceNet complies with CAN based protocol and provides the following features:

• DeviceNet Group 2 Server implementation.
• Bus Powered Network Interface allows power alarm information to be communicated when actuator

loses main power. The actuator does NOT drop off the network when 3-phase power is lost.

• Standard Polled I/O Connection
• Standard Bit Strobed I/O Connection
• Standard Change of State / Cyclic I/O Connection
• Standard explicit connections defined as:

• Various Assembly Objects and sizes that allow the network user to determine how much data to

transfer to accommodate network installation data throughput requirements.

• Automatic BAUD rate detection.
• Node Address configurable via local setup menu, or via the remote network user.
• Broadcast or group network originated ESD support.

The following commands and information may be transmitted over the DeviceNet network:

• “OPEN,” “STOP,” and “CLOSE” commands
• “ESD” and “MOVE–TO” position commands
• Actuator status and alarm messages
• Four digital inputs, two digital outputs, one analog input and one analog output for user configuration
• A surge-protected and isolated communication channels
• UEX control panel configuration

Please see Section 16 for network connection topologies and cabling recommendations.