Limitorque UEX FCD LMENIM1205-03-AQ – 05/15

46

Figure 15.5 – Modbus, F

oundation

Fieldbus, Profibus DP V1, and Profibus PA, and DeviceNet Network Wiring Diagrams

NOTE: CONNECTIONS LANDED TO INTERFACE BOARD.

RECOMMENDED DEVICENET CABLE IS BELDEN 3084A OR EQUAL.

120 OHM, 1/4W TERMINATION RESISTORS MUST BE CONNECTED AT EACH SEGMENT END.

PREFERRED NETWORK WIRING IS TO CONNECT SHIELD TO TERMINAL 3 FOR EVERY UNIT ON SEGMENT.

SHIELD SHOULD BE CONNECTED TO POWER SUPPLY GROUND AT THE CLOSEST POINT IN THE CENTER

OF THE NETWORK.

DeviceNet

DEVICENET BOARD

EGND

RED

WHT

BLK

BLU

NETWORK 0V

NETWORK +24V

NETWORK DATA (–)

NETWORK DATA (+)

SHIELD

J8.5

J8.1

J8.3

J8.4

J8.2

VIA STANDOFF

BLU

WHT

BLK

RED

N/C

F

OUNDATION

FIELDBUS

TERMINALS 29 AND 41 ARE REDUNDANT AND MAY BE USED FOR DAISY CHAIN

CONFIGURATION.

NOTES:

LOSS OF COMMUNICATION ON A1 => REGISTER 9 CHANNEL A

(BIT 0x0400) SET TO 1

LOSS OF COMMUNICATION ON A2 => REGISTER 9 CHANNEL B

(BIT 0x0800) SET TO 1

PREFERRED NETWORK WIRING IS TO CONNECT ONLY ONE SHIELD TO

EARTH/GROUND. REFER TO DDC INSTALLATION DOCUMENTATION.

33

34

28

35

36

NETWORK DATA-A2

NETWORK DATA-A2*

NETWORK DATA-A1

NETWORK DATA-A1*

Modbus BOARD

Modbus

EARTH/GROUND

SURGE PROTECTION

A

REG 9.0x0400

REG 9.0x0800

B

CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN

TERMINAL 3 AND CHASIS GROUND FOR SURGE PROTECTION.

PREFERRED NETWORK WIRING IS TO CONNECT SHIELD TO

EARTH/GROUND AT BOTH ENDS OF THE SEGMENT. ATTACH

SHIELD TO TERMINAL 3 ONLY IF DEVICE IS LOCATED AT THE

ENDS OF THE SEGMENT. CUSTOMER MUST CONNECT REMAINING

INDIVIDUAL NETWORK CABLE SHIELDS TOGETHER TO ENSURE

PROPER SHIELDING OF THE ENTIRE NETWORK.

PBDP1 (+)

PBDP1 (–)

PROFIBUS

DPV1

IEC 61158–2

Profibus DP_V1

SURGE

CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN TERMINAL 3

AND CHASIS GROUND FOR SURGE PROTECTION. PREFERRED NETWORK

WIRING IS TO CONNECT SEGMENT SHIELD TO EARTH/GROUND AT ONE

POINT ONLY. ATTACH SHIELD TO TERMINAL 3 ONLY IF SEGMENT IS NOT

GROUNDED. ELSEWHERE, CUSTOMER MUST CONNECT INDIVIDUAL

NETWORK CABLE SHIELDS TOGETHER TO ENSURE PROPER SHIELDING

OF THE ENTIRE NETWORK.

FF1 (+)

FF1 (–)

FF1 (+)

FF1 (–)

F

OUNDATION

FIELDBUS

IEC 61158–2

F

OUNDATION

Fieldbus_H1

SURGE

CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN TERMINAL 3

AND CHASIS GROUND FOR SURGE PROTECTION. PREFERRED NETWORK

WIRING IS TO CONNECT SEGMENT SHIELD TO EARTH/GROUND AT ONE

POINT ONLY. ATTACH SHIELD TO TERMINAL 3 ONY IF SEGMENT IS NOT

GROUNDED. ELSEWHERE, CUSTOMER MUST CONNECT INDIVIDUAL

NETWORK CABLE SHIELDS TOGETHER TO ENSURE PROPER SHIELDING

OF THE ENTIRE NETWORK.

PBPA1 (+)

PBPA1 (–)

PBPA1 (+)

PBPA1 (–)

PROFIBUS

PA

IEC 61158–2

Profibus_PA

SURGE

PBDP1 (+)

PBDP1 (–)

DDC-100:

JP1 AND JP2 MUST BE IN POSITION “A”. THE 6-[IN CONNECTOR WITH

BLUE WIRES SHOULD BE CONNECTED TO J2 OF THE DDC-100 BOARD.

33

34

28

35

36

33

34

28

35

36

33

34

28

35

36

33
34

28
35
36

TERMINALS 13 &14 FOR FOUNDATION FIELDBUS, PROFIBUS PA, PROFIBUS DP_V1
ARE USED FOR CHANNEL B ON OPTIONAL REDUNDANT NETWORK BOARD.