background image

Limitorque UEX FCD LMENIM1205-03-AQ – 05/15

52

Figure 16.3 – Typical Profibus System with a DCS Host (Daisy Chain Shown)

Distributed Control

System (Host)

Control Highway

Profibus DP

Interface

PB

Actuator

PB

Actuator

PB

Actuator

PB

Actuator

Terminator

Terminator

Profibus DP or PA Network

Segment coupler

Power supply

PA Segment coupler

(PA only network)

16.4 Network Wiring – DeviceNet

Please refer to LMENIM2328 for detailed installation instructions.

DeviceNet is a CAN - based protocol that uses 5 wires including a shield. Two of the conductors are
used for 24V DC power & up to 8 amps (4 amps for NEC Class 2) may be passed along the hi-way from
a suitable power source. Two conductors are used for the CAN bus signals, CAN_H and CAN_L, which
are usually smaller in diameter. Limitorque recommends Belden cable for connecting to a DeviceNet
network. The specifications for thick and thin cable (per site requirements) are as follows: