13 comprehensive indicator index – Flowserve ValveSight Diagnostics User Manual

Page 52

Advertising
background image

ValveSight Diagnostics for HART User Manual FCD VSENSF0001-02-AQ 03/15

52

13 Comprehensive Indicator Index

The following table contains a full listing of the possible Alarms, Alerts, Warnings, and Indicators available in the ValveSight Diagnostics tool.

#

Indicator

Implications

Possible Solutions

Default

Settings

Enable/

Disable

Refer to DTM

Screen:

Blink

Code

0

Initializing

Mode

Displays a blink sequence 3 times

when the unit is powering up.

Wait for power up to complete

N/A

No

N/A

YGGR

1

Factory Re-

set State

Indicates the unit has had a factory

reset and has not yet been calibrated.

The unit will not respond to com-

mands and will remain in the failsafe

position until a calibration is complete.

Calibrate. Proper ValveSight opera-

tion will require stroke, actuator,

and friction calibration to be

completed.

N/A

Yes

N/A

RGRR

2

Digital

Command

Source

Indicates a HART® signal is needed

to change the position command and

the analog 4-20 mA input signal is

ignored.

A manual Command Source Reset

is provided to change the command

back to analog control mode from

the local interface if a PC or hand

held configurator is not available.

This is done while a QUICK-CAL is

in progress by holding down both

the Jog buttons (up and down)

while briefly pressing the QUICK-

CAL button. A new QUICK-CAL

must be done after resetting.

N/A

No

Dashboard

GGYY

3

Squawk

Mode On/

Off

When ON, indicates a user has set the

positioner to flash a special sequence

so that it can be visually located.

This mode is cancelled if the

QUICK-CAL button is briefly

pressed. The Squawk mode is

selected again remotely or if more

than one hour has passed since the

command was issued.

OFF

No

Configuration

> Custom >

LED

GGRR

4

Jog

Command

State

Indicates the unit has been placed in

a local override mode where the valve

can only be stroked using the two

local Jog buttons.

Control the valve using the Jog but-

tons. This mode may be cancelled

by briefly pushing the QUICK-CAL

button.

N/A

No

N/A

YGYY

5

Signature

in Progress

Mode

Indicates that a test has been initiated

by Flowserve supplied software.

Signatures can only be cancelled by

Flowserve supplied software.

N/A

Yes

Diagnostics

YGGY

6

N/A

7

N/A

8

Position

Deviation

Alarm

Indicates the difference between the

command and the actual position has

been greater than the user-set limit for

longer than the user-set time.

Review active alarms and warnings

to find root causes of this alarm.

De-

viation:

110%

Time: 60

Seconds

Yes

Configuration

> Alarms/

Alerts >

Command

Deviation

RRRR

9

Soft Stop

Upper

Limit Alert

Indicates the unit is being commanded

to exceed a user-set upper position

limit and the internal software is

holding the position at the limit. The

function is similar to a mechanical

limit stop except it is not active if the

unit is un-powered.

Reset the limit if more travel is

needed or adjust the command

signal back in the specified range.

110%

NO

Configuration

> Custom >

Soft Limits

GYGY

10

Soft Stop

Lower

Limit Alert

Indicates the unit is being commanded

to exceed a user-set lower position

limit and the internal software is

holding the position at the limit. The

function is similar to a mechanical

limit stop except it is not active if the

unit is unpowered.

Reset the limit if more travel is

needed or adjust the command

signal back in the specified range.

-10%

No

Configuration

> Custom >

Soft Limits

GYGY

11

Position

Upper

Limit Alert

The position has reached or is exceed-

ing a user-set upper position indicator

similar to a limit switch indicator.

Reset the indicator if more travel

is needed or adjust the command

signal back in the specified range.

110%

Yes

Configuration

> Alarms/

Alerts >

Travel Alerts

GYGG

12

Position

Lower

Limit Alert

The position has reached or is exceed-

ing a user-set lower position indicator

similar to a limit switch indicator.

Reset the indicator if more travel

is needed or adjust the command

signal back in the specified range.

-10%

Yes

Configuration

> Alarms/

Alerts >

Travel Alerts

GYGG

Advertising