Field conversion – Flowserve LPC Compact Actuator Series User Manual

Page 11

Advertising
background image

3

Field Conversion

For field conversion from fail open (CCW) to fail close (CW) and vice versa, follow the following steps.

NOTE:

• An additional adapter kit is not required for field conversion
• Disassemble the actuator from the valve before carrying out the conversion

THE ACTUATOR IS DISASSEMBLED FROM THE VALVE

a

WARNING: Ensure that the pneumatic connection ports of the cylinder are disconnected. Also make sure that

all pneumatic supplies to the control unit and all power supplies are disconnected. Finally, make sure that the
actuator is in fail position.

3.0.1

Starting with the actuator in a fail open (CCW) execution,

remove the actuator from the valve, keeping the spool

adaptor installed onto the valve.

3.0.2

Rotate the actuator.

3.0.3

Reassemble in the new position the actuator onto

the spool piece and the valve. Now the actuator is in

a fail close (CW) execution. Similar steps will apply for

conversion from fail close (CW) to fail open (CCW).

11

LPC Compact Actuator Series FCD LFENIM0002-00-AQ 07/14