Flowserve MX-100 Field Unit User Manual

Page 29

Advertising
background image

29

MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

flowserve.com

Example of “Move-To” Command
Move an actuator at address 1 to 50% of open by presetting registers 40001 with the value 6656, and register 40002
with the value 50 in a single write command. The actuator will receive this message and move to a position of 50%
open.

Query: 011000000002041A0000327562

Response: 01100000000241C8

Message Breakdown

Query

Response

01

Slave Address

01

Slave Address

10

Function

10

Function

00

Starting Address Hi

00

Starting Address Hi

00

Starting Address Lo

00

Starting Address Lo

00

No. of Registers Hi

00

No. of Registers Hi

02

No. of Registers Lo

02

No. of Registers Lo

04

Byte Count

41C8

Error Check (LRC or CRC)

1A

Preset Data Hi

00

Preset Data Lo

00

Preset Data Hi

32

Preset Data Lo

7562

Error Check (LRC or CRC)

Note: The single register write “Move-to” command may also be used with the function code 16.

This function code may also utilize the Single Register write “move-to” command.