CONTROLS

Accord Controls

765 South 100 East

Phone: 801 373 4576

A Unit of Flowserve Corporation

Provo, Utah 84606-6160

Facsimile: 801 489 2591

www.accord-controls.com

Class I, Division 2, Applications must be installed as specified in NEC Section 501-4 when barriers are not used.

(Refer to ANSI/ISA RP12.6 for guidance on installation).

Electrical Specifications:

Field Installation:

All input options can be added/changed

in the field without removing positioner cover. Figures 3

and 4 (5100 and 5200/5600 respectively) show mounting

information and location of terminal connections.
Caution:

If I/P Module is installed in explosive atmosphere,

disconnect power prior to removing cover to avoid

personal injury.

1. Remove supply pressure and input signal connection.

2. Remove old I/P Module or pneumatic manifold and

associated hardware.

3. Following applicable figure, install new I/P Module and

associated hardware. Be sure O-rings are in place.

4. Make electrical and pneumatic connections. Do not use

Teflon tape on supply connection fitting. Use only a

liquid or paste non-hardening pipe sealant on

the threads.

5. For intrinsically safe applications (Model 5400 only)

refer to Figure 1 for barrier information and schematics.

6. All I/P Modules are factory calibrated and should not

require adjustment. However, it is recommended that

calibration be checked (see “I/P Module Calibration”).

7. Install cover.

Page 4 of 8

Parameter

Model 5100

Model 5200

Model 5300

Model 5400

Model 5600

Max. Voltage VDC

30

30

28

30

28

Min. Voltage VDC

6

5.5

5.5

5.5

5.5

Max. Current (mA)

50

125

93.3

125

93.3

C (Micro Farad)

1

1

1

1

1

L (Mili Henry)

1

1

1

1

1

Hazardous Locations

Exp. Proof

Exp. Proof

Intrinsically Safe

Intrinsically Safe

CL l,ll, Div 1

EEx d llB+H2

CL l,ll Div 1

EEx ia llC T4

Non-incendive

T6-40 to +40C

Groups B-G

CL l, Div 2

T5-40 to +75C

Groups A-D

T4-40 to 110C

Agency Approval

FM/CSA

SCS

FM/CSA

SCS