I/P Module Calibration: Caution:

If I/P Module is installed in

explosive atmosphere, disconnect power prior to removing
cover to avoid personal injury.

Figures 3 and 4 (5100, and

5200-5600 respectively) show the locations of zero and

span adjustments.

1. Start with cover removed, supply pressure

connected, and a 4 mA input signal.

2. Turn zero potentiometer (pot) until I/P Module gauge

reads 3 psi.

3. Change input to 20 mA and turn span pot until I/P

Module gauge reads 15 psi.

4. Zero and span adjustments are interactive, so repeat

steps 1 thru 3 as necessary.

5. Replace cover.

I/P Module Troubleshooting (Model 5100 only - consult factory for 5200 & 5400):

Problem

Probable Cause/Solution

I/P Module does not build up full output pressure

1. Improper zero/span setting.

regardless of input:

2. Low bias (see “Bias Adjustment”).

3. Air leakage (check O-rings & pneumatic diaphragm).

4. Low air supply.

5. Low regulator output (see “Regulator Adjustment”).

I/P Module does not build up any pressure (or does not

build up over bias pressure):

Circuit Board LED not lit:

1. Loose, shorted, or reversed signal connection.

2. Coil connection reversed.

3. Controller board not responding (replace board).

Circuit Board LED lit:

1. Low bias pressure (see “Bias Adjustment”).

2. Air leakage (check O-rings & pneumatic diaphragm).

3. Bad coil connection or bad coil.

4. Dirty or plugged I/P Module filter (clean or replace).

I/P Module puts out excessive pressure at 4 mA:

1. Improper zero/span setting.

2. High bias (see “Bias Adjustment”).

I/P Module output fluctuates:

1. Air leakage (check O-rings & pneumatic diaphragm).

2. Zero or low bias pressure (see “Bias Adjustment”).

Bias Adjustment:

With supply pressure connected and no

input signal, the I/P Module should put out between 2 and 2

1/2 psi. If necessary, turn the bias adjust setscrew

(CW to increase, item 20 figure 3).
Regulator Adjustment:

With supply pressure connected and

input adjusted to 24 mA or 125 percent, the I/P Module

pressure should be between 18 and 20 psi. If necessary, turn

the regulator setscrew (CW to increase, see figure 3). This

adjustment may affect bias pressure, recheck bias pressure

after making adjustment.

Apex Modular Positioning System (AMPS) Options:

The Apex 5000 positioner is also designed to accept modular

output accessories. These “bolt on” easily and require no

housing modification. The following is a list of part numbers

to specify when ordering.

Electrical Output (Feedback) Options

Base No.

Add Cam Option

Suffix Options - Description

KMA

A-Std. Linear Cam

F - 4-20 mA Transmitter

KMA

B-30,45,60,90

G - 1K OHM Feedback Pot.

KMA

C-Characterized

H - 10K OHM Feedback Pot.

KMS

D-60

°

for butterfly valve

K - 2-SPDT Mechanical Sw.

KMS

M - 2-SPST Proximity Sw.

KMS

N - 2-SPDT Proximity Sw.

Pneumatic Output Options

Part Number

Description

KMFC

Flow Control Module

KMBB

Block/Bleed Module

(Manual Override + lock-out)

KMBBFC

Flow Control + Block/Bleed

Modules

Advertising
This manual is related to the following products: