Storage instructions, Installation, Worcester controls – Flowserve PM15E Electro-Pneumatic Valve Positioner User Manual

Page 2: Actuator positioner

Advertising
background image

1. STORAGE INSTRUCTIONS

PM15E Positioner Storage and Handling Procedures
PM15E positioners are precision instruments which should be stored
and handled accordingly to avoid problems or damage.

Electro-pneumatic positioners contain electronic components which
can be damaged by exposure to excessive water. Appropriate
precautions should be taken to protect units while in storage.

Warehouse Storage
Stored in original shipping containers, units should be stored in an
environmentally controlled area, i.e., clean, cool (15–26°C, 60–80°F)
and dry, out of direct sunlight or weather exposure.

Field Storage
NOTE:
Once the air supply to the positioner is connected and turned
on, internal air bleed will prevent the ingress of moisture and protect
the unit from corrosion. It is recommended that the air supply be left
on at all times.

If units are installed immediately, turn, and leave on, the air
supply.

If positioners must be stored outdoors, tighten all covers which
may have loosened in shipment, make sure all open enclosure
points are sealed.

Positioners should be wrapped and sealed air and watertight with
desiccant inside the plastic; units should be securely covered with an
opaque cover and not exposed to direct sunlight, rain or snow.

Units should have all ports sealed and be protected from direct
exposure to weather. For long term storage (>1 month) or overseas
shipment units should be protected with plastic and desiccant.

Potential Damage to Mechanism
When units are stored in hot, humid climates, the daily
heating/cooling cycle will cause air to expand/contract and be drawn
in and out of the positioner housing. Dependent on the local

temperature variations, humidity and dew points and time in storage,
condensation could occur and accumulate inside on the I/P converter
causing erratic operation or failure due to water and corrosion. The
potential for condensation damage is especially high in southern
climates and aggravated if units are exposed to direct sunlight.

For further assistance, please contact your nearest Worcester
distributor.

2. INSTALLATION

Before mounting the positioner, the relationship of the actuator to the
valve must be determined. The actuator can be mounted in-line or
cross-line to the valve. In addition, the actuator can be mounted right-
side-up or inverted. If a spring-return actuator is used, the actuator
can be set up to fail with the valve closed or with the valve open. This
gives the end user a total of eight possible set-up configurations.

A. Mounting Guide

The following notes pertain to Positioner Mounting Guide below.

1) “Inverted” actuator position and “Cross-Line” actuator

mounting applies to sizes 10–20 39 Series actuators only. On
sizes 25 and larger, the output shaft is square, which allows
for the coupling to be indexed 90° to the actuator shaft.
Normal actuator position means that the actuator is mounted
“right-side-up”.

2) For spring-return actuators only: “Fail-Open” actuators have a

“9” in position 3 of the ordering code.

3) To change cam to reverse-acting, remove and reinstall upside

down (see Section 9).

4) For double-acting actuators only: Normal hose positions

refers to that described in Section 2.C, Connections.

Flow Control Division

Worcester Controls

2

Model PM15E Electro-Pneumatic Valve Positioner

WCAIM2017

Actuator

Valve

Actuator

Failure

Actuator

Supply

Position

Mounting

Mode

Position

Rotation Positioner

Cam

Hoses

at Min.

(Note 1)

(Note 2)

(Note 1)

to Open

Operation

(Note 3)

Cam Setting

Note 4

Signal

In-Line

Fail-Close

Normal

CCW

Direct-Acting

Direct-Acting

0° (Min. Signal) When Valve is Closed

Normal

Closed

In-Line

Fail-Close

Normal

CCW

Reverse-Acting

Reverse-Acting 90° (Max. Signal) When Valve is Closed

Reverse

Open

Cross-Line Fail-Close

Inverted

CW

Direct-Acting

Reverse-Acting 0° (Min. Signal) When Valve is Closed

Reverse

Closed

Cross-Line Fail-Close

Inverted

CW

Reverse-Acting

Direct-Acting

90° (Max. Signal) When Valve is Closed

Normal

Open

In-Line

Fail-Open

Inverted

CCW

Direct-Acting

Direct-Acting

90° (Max. Signal) When Valve is Open

Normal

Closed

In-Line

Fail-Open

Inverted

CCW

Reverse-Acting

Reverse-Acting 0° (Min. Signal) When Valve is Open

Reverse

Open

Cross-Line Fail-Open

Normal

CW

Direct-Acting

Reverse-Acting 90° (Max. Signal) When Valve is Open

Reverse

Closed

Cross-Line Fail-Open

Normal

CW

Reverse-Acting

Direct-Acting

0° (Min. Signal) When Valve is Open

Normal

Open

Actuator

Positioner

Advertising