Automax Logix 3200IQ Digital Positioner

Installation, Operation and Maintenance Instructions

Figure 17: Driver Module Barbed Fitting

10. Disconnect the flexible tubing from the barbed fitting at

the driver module assembly (see Figure 17).

11. Use the 1/4" nutdriver to remove the barbed fitting

from the driver module assembly.

12. Unplug the two wiring connections that link the driver

module assembly to the main PCB assembly.

13. Feed the two wires on the driver module back into the

driver module compartment so that they stick out the
driver module opening (see Figure 14). This will allow
the driver module to thread out without tangling or
cutting the wires.

14. Grasp the base of the driver module and turn it

counterclockwise to remove. After it is threaded out,
carefully retract the driver module from the housing.

Barbed Fitting

Flat on
Housing

Flat on
Driver
Module

Driver Module Cover

Main PCB

Analog Output Board

Pressure Sensor Board

Regulator

Plastic
Board
Cover

Main PCB
Retaining
Screws

Plastic Cover
Retaining Screws

Figure 18: Main PCB Assembly