Commissioning, Fig. 12 – Flowserve NRS 1-50 For ONE Electrode User Manual

Page 19

Advertising
background image

9

Commissioning

- continued -

Checking switchpoint and function

Start

Activity

Indication

Function

Apply

mains voltage.

All LEDs are illuminated.

System is being started and tested,

this takes approx. 0 sec.

Output contacts are open.

Signal outputs  /  are closed.

All LEDs are illuminated for more

than 0 sec.

System malfunction. Possible causes: Faulty

power supply, level switch defective.

Raise water in boiler until

the switchpoint “low water

level (LW)” is ecxeeded. Level

electrode enters the water.

Green LED

for level electrode  is illuminated

Output contacts are closed.

Signal outputs  /  open.

Checking switchpoint and function

Lower water level until it is

below the switchpoint “low

water level (LW)”. Level

electrode is exposed.

Red LED

for level electrode  is flashing

De-energizing delay is running.

Signal outputs  /  are closed instantaneously.

Red LED

for level electrode  is illuminated

Delay time has elapsed, output contacts open.

Signal outputs  /  are closed.

Possible installation faults

Status and indication

Fault

Remedy

Sightglass indicates level

below switchtpoint “low

water (LW)”, red LED for level

electrode  not illuminated.

Safety circuit closed.

Electrode rod is too long.

Cut electrode rod to the length dictated by the

switchpoint LW.

If installed inside the boiler: Upper

vent hole in protection tube does

not exist or is obstructed.

Check installation of level electrode. Make sure

that the level in the protection tube corresponds

to the actual water level.

Water level sufficient.

Red LED for level electrode 

is illuminated. Safety circuit

is open.

The electrode rod is too short.

Replace electrode rod and cut new rod to the

length dictated by the switchpoint LW.

The earth connection to the vessel

is interrupted.

Clean seating surfaces and screw in level elec-

trode with metallic joint ring. Do not insulate

the electrode with hemp or PTFE tape!

Electrical conductivity of the boiler

water too low.

Set response sensitivity of the level switch to

0.5 μS/cm.

Upper vent hole flooded.

Check installation of level electrode. Make sure

that the level in the protection tube corresponds

to the actual water level.

LED alarm  /

operating mode

Level electrode 1

Test & diagnosis

button

LED alarm  /

operating mode

Test & diagnosis

button

Diagnosis LED

Fig. 12