Directives and standards – Flowserve NRS 1-50 For ONE Electrode User Manual

Page 5

Advertising
background image

5

Directives and Standards

Pressure Equipment Directive (PED) 97/23/EC

Water level limiters are safety accessories as defined in the Pressure Equipment Directive (PED).

The level switch NRS -50 in conjunction with level electrode NRG ...-50 and NRG 6-36 is EC type

approved according to EN 95/EN 953. These Directives state, among other things, the require-

ments made on limiting systems and equipment for steam boiler plants and (pressurised) hot-water

installations.

ATEX (Atmosphère Explosible)

According to the European Directive 94/9/EC the level switch NRS -50 must

not be used in potentially

explosive areas.

Note

The level electrodes NRG ...-50, NRG ...- and NRG 6-36 are simple items of elec-

trical equipment as specified in EN 60079- section 5.7. According to the European

Directive 94/9/EC the equipment must be equipped with approved Zener barriers if used

in potentially explosive areas. Applicable in Ex zones ,  (999/9/EC). The equipment

does not bear an Ex marking. The suitability of the Zener barriers is certified in a separate

document. Note that the requirements of the IEC 6508 are not met if the NRG ...-50,

NRG ...- and NRG 6-36 + Zener barriers + NRS -50 are interconnected!

VdTÜV Bulletin “Wasserstand 100” (= Water Level 100)

The level switch NRS -50 in conjunction with the level electrodes NRG ...-50, NRG ...- and NRG

6-36 is type approved according to the VdTÜV Bulletin “Water Level 00”.

The VdTÜV Bulletin “Wasserstand (= Water Level) 00” specifies the requirements made on water level

control and limiting equipment for boilers.

Functional Safety acc. to IEC 61508

The level switch NRS -50 is certified acc. to IEC 6508 only if used in combination with level elec-

trode NRG ...-50 / NRG 6-36 . This standard describes the functional safety of safety-related electri-

cal/electronic/programmable electronic systems.
The equipment combination NRG ...-50 or NRG 6-36 + NRS -50 corresponds to a type B subsys-

tem with Safety Integrity Level (SIL) 3.

Approvals for Marine Applications

The level switch NRS -50 in conjunction with level electrodes NRG 6-50S/NRG 6-S/NRG 6-38S

and NRG 6-39S is approved for marine applications.

We can present approvals issued by Germanischer LLoyd and Lloyd’s Register.

LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility)

The level switch NRS -50 meets the requirements of the Low Voltage Directive 006/95/EC and the

EMC Directive 004/08/EC.

Advertising