Checking level electrode – Flowserve NRS 1-50 For ONE Electrode User Manual
Page 22
Advertising
Measure the electrode voltage in order to check whether the level electrode is immersed or if there is a
malfunction. Please observe
Fig. 15.
≈ 0.7 V
85 Hz !
Checking level electrode
Measuring voltage across level electrode
Note
n
The self-checking routine of the level switch NRS -50 reduces
U
-
to 0 Volt,
if executed cyclically.
U
-
⊥
Malfunction (immersed/alarm)
U
-
2
<
U
-
2
≥
U
-
⊥
≤
U
-
U
-
⊥
exposed
immersed
b
Stand-by input , 4 V DC, for connecting the logic unit SRL
c
Level electrode NRG ...-50, NRG ...-, NRG 6-36