Commissioning, Performance test – Flowserve NRS1-8 User Manual

Page 16

Advertising
background image

6

Apply mains voltage to level switch NRS -8.

Commissioning

Check that the NRS -8 and the associated level electrode are wired in accordance with the wiring

diagram,

Fig. 10, Fig. 11.

Checking wiring

Apply mains voltage

Performance test

. Check length of electrode rod (see installation manual of the level electrode).
. When switching on the mains voltage the green LED

4

should be permanently illuminated,

Fig. 7.

3. Completely open valves of water-level gauge glass on steam boiler.
4. Fill boiler with feedwater ( cm above low level).
5. Fill up with feedwater until the max. water level (high level) is exceeded.The two red LEDs of the

level switch

2

must light up after the response delay.

If the automatic self-testing routing is activitated at this point in time an alarm will only be raised

after twice the response delay has elapsed.
6. You can simulate a high level alarm by pressing the button “TEST I”

3

, with the electrode tip

submerged. Press and hold down the button until the response delay has elapsed. Both red LEDs

2

must then light up.

7. You can also test the self-checking circuitry of the level switch. With the electrode tip submerged,

operate test switch “TEST II/INSPECTION”

1

in the direction of the arrow. After max. two minutes

the two red LEDs

2

should signal high-level alarm. The button “TEST I”

3

must

not be operated

during this test and the level must

not fall below the low level mark.

After the test return switch

1

to its original position. After the response delay the two red LEDs

2

must extinguish.

High-level limiter