Explanatory Notes

– continued –

Function

The level switch NRS -8 is a two-channel unit provided with an automatic self-checking circuitry in

accordance with DIN VDE 06 prEN 5056 (directives for protection circuits). The self-checking is

effected periodically. The test includes the checking of the cable between electrode and level switch and

of the self-checking circuitry (redundancy). The output relays are not influenced by the internal tests.
In addition to this self-checking routine, the level switch can also be tested manually by pushing the

button “Test ”, simulating a defect in the electrode. The test switch “Test /Inspection” is provided for

checking the function of the checking circuitry.
As the circuit of the relay contacts of the level switch is normally closed, alarm will also be signalled in

the event of a mains failure.
The level switch can signal the following three operating conditions:

n

Normal operation (correct level)

n

Alarm (high level)

n

Alarm (malfunction in level switch or electrode)

The green LED indicates power supply. The high level or malfunction alarms are indicated by two red

LEDs. The failure of one channel (loss of redundancy) is signalled by the illumination of a single red LED.
The combination of electrode NRG 6-, NRG 7-, NRG 9- and level switch NRS -8 provides

fail-safe protection against a first fault, i. e. the system will still continue to provide the safety function

even after the occurrence of a first fault.

System components

NRG 16-12

Level electrode

NRG 16-12, PN 40

NRG 17-12

Level electrode

NRG 17-12, PN 63

NRG 19-12

Level electrode

NRG 19-12, PN 60

Design

NRS 1-8
Plug-in unit in plastic case for installation in control cabinets. The terminals in the case are accessible

after loosening two screws and unplugging the unit from its base.
To avoid confusion with other plug-in units of the GESTRA range, inserts are fitted in the bases so that

only the correct unit may be plugged into each base.
The plug-in unit may be snapped onto a 35 mm supporting rail or screwed into position on a mounting

panel.