Technical data – Fronius IG 300 User Manual

Page 73

Advertising
background image

65

Technical data

FRONIUS IG 300 /
400 / 500

Input data

FRONIUS IG 300

FRONIUS IG 400 FRONIUS IG 500

Recommended power supply

20-34 kWp

28-42 kWp

40-52 kWp

MPP voltage range

210 - 420 V

Max. input voltage
(at 1000 W/m²/- 10°C in an open circuit)

530 V

Max. input current

123 A

164 A

205 A

Output data

FRONIUS IG 300

FRONIUS IG 400 FRONIUS IG 500

Nominal output power (P

nom

)

24 kW

32 kW

40 kW

Max. output power

24 kW

32 kW

40 kW

Nominal mains voltage

3NPE x 400 V, +10/-15 % *

Nominal output current

3 x 34,8 A

3 x 46.4 A

3 x 58 A

Nominal frequency

50 +/-0.2 Hz *

Distortion factor

< 5 %

Power factor

1

General data

FRONIUS IG 300

FRONIUS IG 400 FRONIUS IG 500

Maximum efficiency

94,3 %

94,3 %

94,3 %

Euro efficiency

93,3 %

93,4 %

93,5 %

Overnight internal consumption

9 W *

Internal consumption while in operation

49 W

66 W

83 W

Cooling system

Controlled forced-air ventilation

Protection class
(internal housing/external housing)

IP 20 / IP 43

Dimensions l x w x h
IP 20 with base (200 mm)
to upper edge of exhaust pipe

600 x 600 x 2557 mm ***

IP 43 with base (200 mm)

1112.5 x 600 x 2444.5 mm ***

Weight

225 kg

245 kg

265 kg

Permissible ambient temperature
(with 95% rel. humidity)

-20 - 50 °C **

Protective equipment

FRONIUS IG 300

FRONIUS IG 400 FRONIUS IG 500

DC insulation measurement

Warning when R

ISO

< 500 kOHM

DC overvoltage protection

integrated

Protection against reversed polarity

integrated

Manifestation of DC overload

Operating point repositioned

*)

The values shown are defaults: Your FRONIUS IG has been configured specifically to suit
the requirements in your country

**)

If the ambient temperature rises to above 35 °C or thereabouts (depending on voltage at
the solar module), the AC output power is reduced (power derating).

***)

Please visit www.fronius.com for detailed drawings.