installatiOn OF the pOwer sOurCe

2.1

pOsitiOning OF the maChine

Place the machine on a firm, dry and level surface. Where possible, do not allow dust or other

impurities to enter the machines cooling air flow. Preferably site the machine above floor level;

for example on a suitable carriage unit.
Notes for positioning the machine

• The surface inclination should not exceed 15 degrees.

• Ensure the free circulation of the cooling air. There must be at least 20 cm of free space in

front of and behind the machine for cooling air to circulate.

• Protect the machine against heavy rain and direct sunshine.

NOTE!

The machine should not be operated in the rain as the protection class of the machine,

IP23S, allows for outside preserving and storage only.

NOTE!

Never aim metallic grinding spray/sparks towards the equipment.

2.2

COnneCtiOn tO the mains supply

Connection and change of the mains cable and the plug must be carried out only by a
competent electrician. Remove for the mounting of the mains cable the left side plate, seen
from the front of the power source.
The Kempomat power source is equipped with 5 m supply cable without plug. The mains
cable is according to the marking H07RN-F of the norm CENELEC HD22. The mains cable must
be changed if it doesn´t meet local regulations.

2.3

mOunting OF the mains Cable

The cable is entered into the machine through the inlet ring on the rear wall of the machine
and locked with a cable clamp (05).
The phase conductors of the cable are coupled to connectors L1, L2 and L3. The earth

protection coloured green-yellow is coupled to connector marked with earth protection

symbol

. If you are using 5-conductor cable, you must cut the zero conductor to the level of

the cable´s protective shield.
In cables of S type there is protective grounding conductor coloured green-yellow.

L1
L2
L3

Kempomat

2500

3200

4200

Connection voltage

230 V

400 V

230 V

400 V

230 V

400 V

Connection cable

4G2.5 (5 m) 4G2.5 (5 m) 4G2.5 (5 m) 4G2.5 (5 m) 4G6.0 (5 m) 4G2.5 (5 m)

Fuse, delayed

16 A

10 A

20 A

16 A

25 A

16 A

4

Kempoma

t 2500, 3200, 4200 / © Kemppi O

y / 1117