6.3. DIAGNOSTIC MESSAGES

For diagnostic messages in the Indicating transmitter display, see the PR-01-S manual. The following mes-
sages appear only in divert systems:

-

"In divert control operation" or "Removed from divert control", Section 2.6.

-

"Solids warning" and "Solids alarm", Section 5.4.

-

** Divert control fault **

This message indicates that there is no communication to the divert control unit, probably cable error, Figure
3.12, cable 2.

If the instrument is not applied in a divert control system, de-activate the divert function, see end of Section
5.2.

Further the message ** Relay unit fault ** may appear. This indicates that the Relay unit PR-7080 functions
are defined, but no Relay unit is connected. Normally a Relay unit is not used in a Divert system because the
wash contacts are in the Divert control unit. Clear the relay functions by the key sequence Calibrate/Relay unit
and select an "0 Not Defined" for all four relays. For using an optional relay unit, see PR-01-S Manual, sec-
tion 9.1.

6.4. DIAGNOSTIC LIGHTS

The Divert circuit board, Figure 3.12, contains the following diagnostic LEDS:

D3

Processor cycles: should flash

D4

Processor reads serial bus: should flash

D10

Serial bus A input: should flash

D11

On if 24 V DC supply from A is OK

D12

Serial bus B input: should flash

D13

On if 24 V DC supply from B is OK

D14

On if external 24 V DC is applied

D19

Wash relay A on

D20

Wash relay B on

D21

Solids warning relay on

D22

Solids alarm relay on

D23

Divert relay on = not DIVERT (Section 2.2)

D24

Horn

on

D25

Refractometer

difference

relay on = difference alarm

D26

Override

D27

Valve to bypass

D28

Valve to burner

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5

Effective: June 20, 2005