Assignment of cf segment in ieee1344 mode – Meinberg TCG510 User Manual

Page 8

Advertising
background image

8

Assignment of CF Segment in IEEE1344 mode

Bit No.

Designation

Description

49

Position Identifier P5

50

Year BCD encoded 1

low nibble of BCD encoded year

51

Year BCD encoded 2

52

Year BCD encoded 4

53

Year BCD encoded 8

54

empty, always zero

55

Year BCD encoded 10

high nibble of BCD encoded year

56

Year BCD encoded 20

57

Year BCD encoded 40

58

Year BCD encoded 80

59

Position Identifier P6

60

LSP - Leap Second Pending

set up to 59s before LS insertion

61

LS - Leap Second

0 = add leap second, 1 = delete leap second

1.)

62

DSP - Daylight Saving Pending

set up to 59s before daylight saving changeover

63

DST - Daylight Saving Time

set during daylight saving time

64

Timezone Offset Sign

sign of TZ offset 0 = '+', 1 = '-'

65

TZ Offset binary encoded 1

Offset from IRIG time to UTC time.

Encoded IRIG time plus TZ Offset equals UTC

at all times !

66

TZ Offset binary encoded 2

67

TZ Offset binary encoded 4

68

TZ Offset binary encoded 8

69

Position Identifier P7

70

TZ Offset 0.5 hour

set if additional half hour offset

71

TFOM Time figure of merit

time figure of merit represents approximated

clock error.

2.)

0x00 = clock locked
0x0F = clock failed

72

TFOM Time figure of merit

73

TFOM Time figure of merit

74

TFOM Time figure of merit

75

PARITY

parity on all preceding bits incl. IRIG-B time

1.)

current firmware does not support leap deletion of leap seconds

2.)

TFOM is cleared, when clock is synchronized first after power up. see chapter Selection of generated timecode

Advertising
This manual is related to the following products: