Section 3-3-1: venting layout, Installation – Montigo H38DF PRC User Manual

Page 13

Advertising
background image

H*38DF PRC Panorama Indoor Gas Fireplace

Page 13

XG0211 - 150204.1

Installation

MTKOG (5"/8")

Installing Heat Guards over Terminations

is recommended

in installations where the termination is located within 7' feet above

grade, or above a pedestrian walkway, and may be Required by code

in Public areas.

1. Ensure that the two long mounting brackets are facing the bottom

of the termination. (See inset). This will provide more heat protection

at the top of the termination, where temperatures are highest.

2. Attach to the faceplate of the termination using four sheet metal

screws.

Figure 11. Installing a PTO termination heat guard.

Figure 12. H38PR* or HL38PR* Top Vent Venting Graph for wall mounted

terminations.

Section 3-3-1:

VENTING LAYOUT

Selection of components and details of venting layout should

adhere to the following guidelines:

„

Vent terminations must not be recessed in walls or siding.

„

For Heat Shield requirements see Section 3-3-3 on page 17.

„

Once the proposed venting layout has been determined refer to

either Figure 12, 12a, 14, or 14a to ensure the layout is acceptable.

Notes Wall Mounted Terminations: TOP VENT

„

All dimension lengths for vertical or horizontal runs are measured

from center of the vent pipe.

„

Venting runs must fall within the limits set by the venting graphs,

see Figure 12 or 12a.

Figure 12a. H38PR* or HL38PR* Top Vented, wall mounted installation with

one 90° bend. The vent run must comply with Venting Graph for Top vent, wall

mounted terminations, Figure 12.

42”

46”

A

C

B

If your installation does not fall with-

in the venting graph parameters,

please contact a local Montigo

dealer for Power Venting options.

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

Heat

Shield

Termination

Hearth

Exterior

Wall

46”

Min.

42” Max.

Flex section

The Venting Graph

Measure the vertical height from the fireplace hearth to the centre of

the termination and the horizontal run from the fireplace flue collar to

the wall flange of the termination. Plot on the Venting Graph Figure 12

or 12a with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.
Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 126" and the horizontal

run to the wall flange of the vent termination is 144", this would be

an acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 48" and the horizontal

run to the wall flange of the vent termination is 72", this would

NOT be an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 60" and

the horizontal run to the wall flange of the vent termination is 144",
this would NOT be an acceptable installation.

Advertising
This manual is related to the following products: