Installation, Installing the fireplace shell – Montigo C42DV User Manual

Page 3

Advertising
background image

Page 3

C42-DV Gas Fireplace

®

Part No. XG0119C

Installing The Fireplace Shell

The fireplace may be installed in any location that maintains proper
clearance to air conditioning ducts, electrical wiring and plumbing.
Safety, as well as efficiency of operation, must be considered when
selecting the fireplace location. Try to select a location that does not
interfere with room traffic, has adequate ventilation, and offers an
accessible pathway for Direct Vent installation. Refer to page 4 -

Vent

Installation for more information.

The fireplace dimensions are shown below:

Installation

When installing a shelf over the top of the fireplace, the following
guidelines must be adhered to: For Rear Vent models (C42-DR),
the minimum clearance from the top of the fireplace to a shelf is 8". For
Top Vent models (C42-DT), the minimum clearance is 15". (

Minimum

1" clearance must still be maintained around the vent pipes.)

Figure 4.

Framing for shelves over the fireplace.

Top Vent

Rear Vent

Figure 3.

Corner framing dimensions.

Figure 2.

Framing dimensions.

* When sheetrock is
not used behind the
fireplace, framing
depth may be
reduced to 17 1/4"

Framing

WARNING:

When this appliance is installed directly on carpeting, tile or any
combustible material other than wood flooring, it must be installed
on a metal or wood panel extending the full width and depth of
the appliance.

Top Vent

Front View

Rear Vent

Clearances

These clearances apply to all dimensions

except the framed opening,

where the clearance to combustibles is 0". The C42-DV clearances to
combustible materials are:

Top - Rear Vent*

8"

Top - Top Vent

15"

Back

1/2"

Flue

1"

Side

1"

Floor

0"

Mantle**

8"

*

Clearance from the top of the fireplace to a combustible
ceiling within the fireplace enclosure.

** Refer to page 11.

Unprotected combustible walls which are perpendicular to the
fireplace opening, must not project beyond the shaded area shown in
Figure 19b.

For protection against freezing temperatures, it is recommended that
outer walls of the chase be insulated with a vapour barrier. This will
reduce the possibility of a cold-air convection current on the fireplace.

Figure 1.

Fireplace dimensions.

1 6 ¾

3 2 ½

3 8 ¾

8

5

3 2 ½

4 7

4 2 ¾

4 2 ¾

H e a d e r

S h e lf

H e a d e r

S h e lf

1 5 " .

M in

8 ” M in .