Installation, B. vertical (through-the-roof) installations, Vent restrictors – Montigo C42DV User Manual

Page 8

Advertising
background image

Page 8

C42-DV Gas Fireplace

®

Part No. XG0119C

Part

Size

5/8 Venting 4/7 Venting

A - Termination

n/a

PVTK-1

MVTK-1

B - Flex sections

12

PFL-1

MFL-1

24

PFL-2

MFL-2

36

PFL-3

MFL-3

48

PFL-4

MFL-4

C - Solid sections

12

EXT-1

MEXT-1

24

EXT-2

MEXT-2

36

EXT-3

MEXT-3

48

EXT-4

MEXT-4

D - Support Ring

& Plate

PSPXT-8

MSPXT-7

E - Firestop

PS-8

FS-7

F - Roof Flashing

(1/12 - 7/12 pt.)

PRF-7

MRF-7

(7/12 - 12/12 pt.)

PRF-12

MRF-12

G - Adaptor

(5/8 - 4/7)

Storm collar

Support ring

MEXT
Solid Section

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Firestop

2' min.

MXT-10

Adaptor

MEXT

Flue

Collar

2' min.

Storm collar

Support ring

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Installation

B. Vertical (Through-The-Roof) Installations

5/8" with option for 4/7"

n

Vertical rise >12' can be reduced

n

Vertical Terminations must be installed:

minimum 2' (two feet) above the highest point where
vent passes through the roof.

minimum 6' (six feet) from a mechanical air inlet

minimum 18" (1 1/2 feet) from a parapet wall.

n

Maximum vent height is 35 feet above fireplace.
Note: Flame characteristics will change if the maximum vent height
is used.

n

Minimum clearances 1" from vent to all combustible materials must
be maintained.

Figure 13.a

Straight, vertical venting using required adaptor.

n

A maximum of two offsets (each offset has two 90° bends) may be
made and shall not exceed total length of 25% of the vertical vent height,
when measured center to center of piping.

Example:

Typical vent installation.
20' vertical vent
2 - 2' offsets required
25% of 20' = 5' max. offset allowed

This venting configuration meets requirements.

Figure 14a.

Vertical venting with 1 offset (1 offset= two 90° bends).

Rigid Section

A

A.Male/Female
B.Female/Female
C.Male Flue Collar

B

C

Figure 13b.

Reducing Vertical Vent from 5/8" to 4/7".

Vent Restrictors

When venting vertically, Vent Restrictors may be added to enhance the
burn characteristics of the fireplace.

35' max

35' max

Advertising
This manual is related to the following products: