6.8 TEST Mode

• Test operation can be performed using the test mode.

(1) Operation method

• Set the CM 25 to standby mode, turn DIP switch 3-1 ON, then turn on the unit. The unit will

automatically operate at the following conditions.

- Compressor speed: 90 rps

- Cool mode

- Fan mode: RUN

- Fan speed: HI

< NOTE >

The WMC (or MWT) will be rendered inoperative.

(2) Quit

• Turn DIP switch 3-1 OFF.

CM 25 operation will stop, and the system will shift to standby status.