Technical specificatons – MovinCool Classic Plus 14 User Manual

Page 32

Advertising
background image

32

TECHNICAL SPECIFICATONS

ITEMS/FEATURES

Classic Plus 14

Classic Plus 26

Rating Conditions

Dry bulb

Wet bulb

Humidity

95 °F (35 °C)

83 °F (28 °C)

60 %RH

95 °F (35 °C)

83 °F (28 °C)

60 %RH

Specifications

Power frequency

Line voltage

Power consumption

Current consumption

Power factor

Starting current

Power wiring

60 Hz

Single Phase 115 V

1.30 kW

11.9 A

95 %

52 A

14 (3-core) AWG

60 Hz

Single Phase 208/230 V

2.40/2.40 kW

11.8/10.8 A

98/97 %

41/44 A

12 (3-core) AWG

Cooling Unit

Cooling capability

Cooling system

13,200 Btu/h

(3,890 W)

Direct Expansion

24,000/24,000 Btu/h

(7,060/7,060 W)

Direct Expansion

Blower

Type of fan

Air volume: Evaporator (high)

Evaporator (low)

Condenser (high)

Condenser (low)

Motor output:High

Low

Centrifugal Fan

440 CFM (748 m³/h)

380 CFM (646 m³/h)

880 CFM (1,496 m³/h)

760 CFM (1,292 m³/h)

0.24 kW

0.19 kW

Centrifugal Fan

673/708 CFM

(1,141/1,200 m³/h)

570/600 CFM

(966/1,017 m³/h)

1,215/1,250 CFM

(2,059/2,119 m³/h)

1,155/1,190 CFM

(1,958/2,017 m³/h)

0.56 kW

0.46 kW

Compressor

Type

Output

Refrigerant type

Refrigerant capacity

Hermetic Rotary

0.91 kW

R-410A

1.65 lb (0.75 kg)

Hermetic Scroll

1.47 kW

R-410A

2.31 lb (1.05 kg)