SECTION 2.0: MODBUS MEMORY MAP

ONICON F-5100 Thermal Mass Flow Meters provide flow rate data, totalized flow data, temperature
and zero calibration data via the MODBUS RTU RS485 serial communications interface. MODBUS data
is available in the same engineering units shown on the meter’s display.

Network addressing, Baud rate and parity are also set via MODBUS registers. Refer to the preceding
section for more information on changing these register values.

2.1 MODBUS REGISTER FORMAT AND NETWORKING INFORMATION

All registers are 16 bit MODBUS Holding Registers.

Register address 001 corresponds to memory location 000.

Registers with 200 series addresses are 16 bit unsigned integers.

Registers with 300 series addresses are unsigned 32 bit long integer values

Registers with 500 series addresses are (IEEE754) 32 bit single precision floating point values.

Registers with 800 series addresses are scaled unsigned 32 bit long integer values

MODBUS function codes supported:

Code Description
03

Read Holding Registers

16

Write Multiple Registers

17

Report Slave ID

REGISTER

ADDRESS

DESCRIPTION REGISTER

RANGE

DATA

RANGE

OVER

RANGE

READ/WRITE

COMMENT

349

Baud Rate &

Parity

0 - 65535

0 - 5

Not

Applicable

Read / Write

See Section

1.5.1

REGISTER

ADDRESS

DESCRIPTION REGISTER

RANGE

DATA

RANGE

OVER

RANGE

READ/WRITE

COMMENT

257

Device Address

0 - 65535

01 - 240

Not

Applicable

Read / Write

See Section

1.6.1