ONICON F-5100 MOD Network User Manual

Page 12

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-5100-MOD Flow Meter Network Interface Installation Guide 05/14 - 0669-6

Page 12

REGISTER

ADDRESS

DESCRIPTION

REGISTER TYPE

READ / WRITE

COMMENT

313

Flow Total - part 1

Long Integer (1 of 2)

Read / Write

Write 0 to reset

total.

314

Flow Total - part 2

Long Integer (2 of 2)

Read / Write

REGISTER

ADDRESS

DESCRIPTION

REGISTER TYPE

READ / WRITE

COMMENT

579

Flow Rate - part 1

Floating Point (1 of 2)

Read Only

580

Flow Rate - part 2

Floating Point (2 of 2)

Read Only

581

Temperature - part 1

Floating Point (1 of 2)

Read Only

582

Temperature - part 2

Floating Point (2 of 2)

Read Only

583

Zero Cal. - part 1

Floating Point (1 of 2)

Read Only

584

Zero Cal. - part 2

Floating Point (2 of 2)

Read Only

REGISTER

ADDRESS

DESCRIPTION

REGISTER TYPE

READ / WRITE

COMMENT

835

Flow Rate - part 1

Scaled Long Integer (1 of 2)

Read Only

Multiply long

integer by .001 to

read value.

836

Flow Rate - part 2

Scaled Long Integer (2 of 2)

Read Only

837

Temperature - part 1

Scaled Long Integer (1 of 2)

Read Only

838

Temperature - part 2

Scaled Long Integer (2 of 2)

Read Only

839

Zero Cal. - part 1

Scaled Long Integer (1 of 2)

Read Only

840

Zero Cal. - part 2

Scaled Long Integer (2 of 2)

Read Only