1.3 SPECIFICATIONS

MODBUS RTU NETWORK INTERFACE

RS485

Transceiver:

2-wire, half-duplex

Data format:

8 bit with 1 stop bit

Parity:

Even, none or odd (default: even)

MAC address (device address) range: 1 - 240 (Default: 048)

Baud rate:

9600 or 19200 (Default: 19200)

Termination: None

Biasing:

None

SECTION 1: INTRODUCTION

1.1 PURPOSE OF THIS GUIDE

The purpose of this guide is to provide installation and commissioning procedures and basic
operating and servicing instructions for the ONICON F-5100 Flow Meter MODBUS RTU serial
interface.

1.2 TYPICAL F-5100 INSTALLATION

The F-5100 is a thermal mass flow meter that measures gas flow, provides a local indication of
the flow rate and total, and provides this data via a MODBUS RTU RS485 serial interface to the
utility or building control network.