ONICON D-100 LonWorks User Manual

Page 12

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100-LON Network Interface Installation Guide 05/14 - 0658-4 / 18342

Page 12

1.7.3 Input Network Variables

The D-100-LON Flow Display receives remote commands to reset totals from the network

using Standard Network Variable Types (SNVTs). The input network variables are in ASCII

format. They are used to zero the flow and auxiliary pulse totals transmitted in the output

variables listed in section 1.7.1.

The ASCII character reset input network variables are described in the table below.

Column 1 contains a brief description of the network variables. Column 2 contains the

network variable names. Column 3 contains the Lon SNVT used for each variable. Column

4 contains the ASCII single characters that must be transmitted to the meter along with a

description of what they indicate.

ASCII RESET INPUT NETWORK VARIABLES

Description

Variable Name

SNVT Name

Valid Characters*

Reset Energy-1**

nviResetBTU1a

ANVT_char_ascii

Write an ASCII 1 (49) to reset the selected

total. Once the total has reset, change the

value to back to ASCII 0 (48).

Reset Volume-1

nviResetVol1a

SNVT_char_ascii

Reset Energy-2**

nviResetBTU2a

SNVT_char_ascii

Reset Volume-2

nnviResetVol2a

SNVT_char_ascii

Reset Auxin1 (Di3)

nviResetAuxIn1a

SNVT_char_ascii

*Systems that are not set to decode ASCII characters will use and display the decimal equivalent. These values
are shown in parentheses.

** These variables are present but not used by the standard D-100.

1.7.4 Node Object Network Variables

The D-100 LON Flow Display node object utilizes one output network variable and one

input network variable. These are described in the table below.

NODE OBJECT NETWORK VARIABLES

Description

Variable Name

SNVT Name

Node object control input

nviRequest

SNVT_obj_request

Node object response output

nvoStatus

SNVT_obj_status

1.7.4.1 nviRequest

Five input variable requests have been implemented. These are listed in the table

on the next page. Three of the requests are mandatory functions. They are

Normal, Update Mask and Report Mask. The other two are used to reset totals in

the Btu meter. They are Reset and Clear Reset.

The requests can be used on the node object or on selected function blocks. The

tables on the next page describe the requests and the function blocks associated

with totals in the display.