D-100-LON Network Interface Installation Guide 05/14 - 0658-4 / 18342

Page 5

1.3 SPECIFICATIONS

LON TALK NETWORK INTERFACE

Twisted Pair / Free Topology

Transceiver: TP/FT-10F, 2-wire, non-polarized, transformer isolated connection

Device Address: 48-bit Neuron ID

Communications Rate: 78 kbps

Termination: None provided

Maximum Lead Length: 1640 ft (500m) free topology

SECTION 1: INTRODUCTION

1.1 PURPOSE OF THIS GUIDE

The purpose of this guide is to provide installation and commissioning procedures and basic

operating and servicing instructions for the ONICON D-100 Flow Display.

1.2 TYPICAL D-100 FLOW DISPLAY

The D-100 is a totalizing display module that provides a local indication of liquid, gas or steam

flow rate and total data. It can also be provided with an optional LonWorks serial interface to

communicate data to the building control network.

D-100

SCROLL RESET PROGRAM

ONICON

3864

Steam

Building

Domestic Water Supply

Flow rate and total data to

Data Acquisition System or

Building Control System

120VAC or 24VAC