1.5 RS485 BIASING AND TERMINATION

The ONICON D-100-P1 does not provide biasing voltage or termination to the RS485 network. A
120W termination resistor should be used when the display is installed at the end of the line.

1.6 NETWORK ADDRESSING

Before the D-100 can communicate on the P1 network, the appropriate device address must be
programmed into the display. The P1 network address for ONICON D-100 Flow Displays may
be set to any address from 1 to 99. This address is set at the display. Section 1.6.1 details the
procedure for changing this address.

1.6.1 Changing the Device Address

Every ONICON D-100 is individually programmed at the factory with application specific
data provided by the customer during the ordering process, and this may include network
addressing information. If the device address information was provided, the display
will be programmed with that number. If no address is provided, ONICON displays are
programmed with a default address of 017. The address may be changed at the D-100
using the procedure outlined in the table below.

STEP

ACTION

REACTION

COMMENT

0

Obtain a device address from the
network administrator.

The device address is
a three digit number
between 1 - 99, excluding
zero.

1

With the display running, open
the front panel and locate switch
DEV ADD/PROG ENAB. Press
DEV ADD/PROG ENAB and then
release it.

None

The DEV ADD/PROG ENAB
is located on the processor
board. (See appendix page
A-1.)

2

Close the front panel.

3

Press the PROGRAM button. (If
you do not press the PROGRAM
button, the display will revert to
the RUN mode after 5 minutes.)

The D-100 changes to
PROGRAM mode and the
DEVICE ID page will
appear with the first digit
of the address flashing.

The PROGRAM button is on
the front panel.